General
YCQ9HB ATS appliances are suitable for AC 50Hz, rated working voltage 400V and below, rated current 10A to 63A dual power supply system, the power supply system of the twopower sources: common power supply (N) and standby power supply (R) at the same time detection, when the power supply occurs undervoltage, phase failure power supply failure that is, automatic switching from the abnormal power supply to the normal power supply (can also be manually switched), to enhance the continuity and reliability of the power supply system in the use of the premises.
This improves the continuity, safety and reliability of the power supply system at the place of use.Switching appliances are widely used in power systems, hospitals, postal and telecommuni- cation, firefighting, hotels, banks, airports, wharves, residential neighborhoods, TV stations, facilities, shopping malls and other important places where the continuity of power supply is required.
Standards: IEC 60947-6-1.
Operating conditions
1. The ambient air temperature is -5 °C ~ +40 °C, and the average temperature within 24h does not exceed 35 °C.
2. The altitude of the installation site does not exceed 2000m above sea level.
3. The relative humidity of the air at the installation site should not exceed 50% at an ambient temperature of +40°C. Higher relative humidity is possible at lower temperatures. For example, in the wettest month with an average minimum temperature of +20°C, the monthly average maximum relative humidity for that month can be up to 90%. Appropriate measures should be taken to prevent condensation due to tem- perature changes
4. The pollution level is 3. There is no danger of explosion in the surrounding air, and there are no gases or conductive dust that could corrode metals and destroy insulation.
5. The installation category is III.
6. The two power lines are connected to the upper end of the switching appliance and the load line is connected to the lower end, and must not be reversed.
7. The installation site should be free from significant vibration and shock.
Technical data | |
Model Specification Technical data | YCQ9HB-63 |
Rated working current le | 10A, 16A, 20A, 25A, 32A, 40A, 63A |
Rated working voltage Ue | AC 230V/50Hz (2P), AC 400V/50Hz (3P, 4P) |
Rated insulation voltage Ui | 500V |
Rated impulse withstand voltage Uimp | 4kV |
Rated short-circuit making capacity | 9.18kA |
Rated making and breaking capacity | 6kA |
Mechanical life | 10,000 times |
Electrical life | 3000 times |
Usage category | AC-33iB |
Electrical grade | CB grade |
Pole | 2P, 3P, 4P |
Delay time | 0 ~ 30s adjustable |
Electromagnetic compatibility environmen | Environment B |
Pollution degree | 3 |
protection class | IP30 |
Installation | Vertical Fixed Installation |
operating method | Automatic / Manual |
switch position | Common position ( I ),Standby position ( II ), Disconnect position (0) |
Rated control power | AC 230V/50Hz |
Power supply voltage | Undervoltage switching: 165V±10% |
Control | Loss of voltage/phase out, undervoltage, overvoltage switching |
Controller Functions | |
Control function | |
Auto/Manual Conversion Mode | |
dichotomous | |
Grid - Power Grid | |
Grid -- generators | |
self-referral | |
abandon oneself and not return | △ |
serve as a backup | △ |
Monitor common power supplies and failover | Phase failure/loss of voltage, undervoltage, overvoltage faults |
Monitor backup power and failover | Phase failure/loss of voltage, undervoltage, overvoltage faults |
Fire control input (passive) | |
Fire Feedback Output | |
Adjustable delay time | |
conversion delay | 0s-30s adjustable |
Return delay | 0s-30s adjustable |
Common and standby closing indication | |
Common and standby power indication | |
malfunction alarm | |
overvoltage conversion | |
Undervoltage conversion | |
Loss of Pressure Conversion | |
Out-of-phase conversion | |
communication function | |
Display Module | light-emitting diode |
Note: " " means this function is available; " " means this function is optional; " △ "means Customers require factory adjustments.
Product Structure Schematic
![Power AC 230V/400V Manual Change Over Reliable 63A Dual Automatic Transfer Switch](http://img9.grofrom.com/www.yselectricgroup.com/226f3j00bjEkWUMcsura/Power-AC-230V-400V-Manual-Change-Over-Reliable-63A-Dual-Automatic-Transfer-Switch.webp)
![Power AC 230V/400V Manual Change Over Reliable 63A Dual Automatic Transfer Switch](http://img9.grofrom.com/www.yselectricgroup.com/226f3j00bZEkhHCFgpgQ/Power-AC-230V-400V-Manual-Change-Over-Reliable-63A-Dual-Automatic-Transfer-Switch.webp)
Description of Controller Indicator Messages
Product status | 1 | 2 | 3 | 4 |
Common power supply normal | Ever Bright | |||
Common power closing | Ever Bright | |||
Backup power supply normal | Ever Bright | |||
Standby power closed | Ever Bright | |||
Commonly used circuit breaker release | Adorable | Adorable | ||
Spare circuit breaker release | Adorable | Adorable | ||
Standby conversion delay | Adorable | |||
Standby constant return delay | Adorable | |||
Product Conversion Failure | Adorable | Adorable | ||
Fire switch | Adorable | Adorable |
• 101#, 102# commonly used power supply external indication signal output (AC220V/0.5A active), 3P products commonly used zero line con- nected to the 101# terminal ;
• 103#, 104# common closing external indication signal output (AC220V/0.5A active) ;
• 201#, 202# standby power external indication signal output (AC220V/0.5A active), 3P products standby zero line connected to 201# terminal ;
• 203#, 204# common closing external indication signal output (AC220V/0.5A active) ;
• 301#, 302#, 303# for generator start control signal passive output terminal, 301# for the public terminal, 302# for the normally closed terminal ; 303# for the normally open terminal, common power supply is normal when 303# and 301# closed, 302# and 301# disconnected ; common power supply is abnormal when 302# and 301# closed, 303# and 301# disconnected ;
• 401 #, 402 # for the fire linkage signal passive input, the port can only be connected to a set of external passive normally open contacts (if the fire signal is an active signal, must be transferred through a small relay relay normally open contacts into the port) when the external contact closure controller immediately after control
• 403# and 404# are passive output terminals for firefighting feedback signals. Under normal condition, the ports are normally open, and 403# and 404# are closed when there is a firefighting signal input to the controller to make the switch switch switch to the breaking position ;
• 501#, 502#, 503# are communication function consoles.